What is standard EN 442 Delta-T 50°C?
EN 442 rates radiators at 75°C flow, 65°C return and 20°C room temperature, yielding an arithmetic mean temperature difference (Delta-T) of 50°C.
Calculate required panel radiator length and heating capacity (Watt / kcal/h) for rooms based on area, ceiling height and EN 442 temperature regimes.
Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.
Thermal output in Watts and kcal/h for standard 75/65/20°C and low-temperature condensing 55/45/20°C regimes.
| Room Area (m²) | Radiator Length (Type 22) | Output at 75/65/20°C (W) | Output at 75/65/20°C (kcal/h) | Condensing 55/45/20°C (W) |
|---|---|---|---|---|
| 8 – 10 m² | 600 mm (0.6 m) | 1,004 W | 863 kcal/h | 518 W |
| 11 – 14 m² | 800 mm (0.8 m) | 1,339 W | 1,151 kcal/h | 691 W |
| 15 – 17 m² | 1000 mm (1.0 m) | 1,674 W | 1,440 kcal/h | 864 W |
| 18 – 21 m² | 1200 mm (1.2 m) | 2,009 W | 1,728 kcal/h | 1,037 W |
| 22 – 25 m² | 1400 mm (1.4 m) | 2,344 W | 2,016 kcal/h | 1,210 W |
| 26 – 30 m² | 1600 mm (1.6 m) | 2,678 W | 2,303 kcal/h | 1,382 W |
| 31 – 36 m² | 2000 mm (2.0 m) | 3,348 W | 2,879 kcal/h | 1,728 W |
EN 442 rates radiators at 75°C flow, 65°C return and 20°C room temperature, yielding an arithmetic mean temperature difference (Delta-T) of 50°C.