Panel Radiator Sizing Guide: Type 11, 21, 22, and 33 Heat Output

How to size steel panel radiators (EN 442) based on room heat loss and water temperature regimes (75/65/20°C vs condensing 55/45/20°C).

✍️ Emre Cevahir Korkmaz (Mechanical Engineer) 📅 2026-08-06 ⏱️ 5 min read

Proper sizing of steel panel radiators ensures indoor thermal comfort and maximizes condensing boiler efficiency.

What Do Type 11, 21, 22, and 33 Mean?

Panel radiators are classified by the number of water-filled heating panels and convector fins:

  • Type 11 (PK): 1 Panel, 1 Convector fin
  • Type 21 (PKP): 2 Panels, 1 Convector fin
  • Type 22 (PKKP): 2 Panels, 2 Convector fins (Industry standard for residential & commercial heating)
  • Type 33 (PKKPKP): 3 Panels, 3 Convector fins (High thermal output for compact wall spaces)

Sizing for Condensing Boilers (55/45°C vs 75/65°C)

Catalog outputs under EN 442 are rated at ΔT = 50 K (75/65/20°C), where a 1-meter Type 22 (H=600 mm) radiator delivers approximately 1,674 W (1,440 kcal/h). For low-temperature condensing systems (55/45/20°C, ΔT = 30 K), thermal output drops to ~52% of nominal rating, requiring longer radiators to achieve full flue gas condensation.

Calculate exact radiator length by room area with our Panel Radiator Sizing Calculator.