Building Thermal Insulation & U-Value Calculation Guide (TS 825 / ISO 6946)

How to calculate overall thermal transmittance (U-value) and select optimal insulation thickness using EPS, XPS, or Rockwool under TS 825 and EN ISO 6946.

✍️ Emre Cevahir Korkmaz (Mechanical Engineer) 📅 2026-07-16 ⏱️ 4 min read

Minimizing heating and cooling energy demand in buildings requires strict compliance with thermal insulation standards such as TS 825 and EN ISO 6946.

Thermal Transmittance (U-Value) and Resistance (R)

The overall heat transfer coefficient (U-value, in W/m²·K) measures the rate of heat transfer through 1 m² of a building envelope element per degree Kelvin temperature difference:

U = 1 / (Rsi + R1 + R2 + ... + Rn + Rse)

Each layer's conductive thermal resistance is calculated from its thickness (d, m) and thermal conductivity (λ, W/m·K):

R = d / λ

Comparing EPS, XPS, and Rockwool

  • EPS (Expanded Polystyrene): Cost-effective facade insulation (λ ≈ 0.035–0.040 W/m·K).
  • XPS (Extruded Polystyrene): High compressive strength and low moisture absorption (λ ≈ 0.030–0.035 W/m·K), ideal for foundations and inverted roofs.
  • Rockwool (Mineral Wool): Class A1 non-combustible fire resistance with superior acoustic damping (λ ≈ 0.035–0.040 W/m·K).

Check condensation risk and required thickness instantly with our Building Thermal Insulation Calculator.