What is the maximum allowed gas velocity in building pipes?
According to standards, natural gas velocity in low-pressure indoor installations is restricted to a maximum of 6 m/s to prevent whistling and regulator wear.
Calculate internal gas pipe diameter, gas velocity and allowable pressure drop for low-pressure (21 mbar) natural gas pipelines.
Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.
Approximate natural gas flow capacity (Nm³/h) and thermal load (kW) for 21 mbar low-pressure lines (ΔP ≤ 1.0 mbar).
| Pipe Size (DN) | Inch Size | Inner Dia (mm) | Max Gas Flow (Nm³/h) | Thermal Capacity (kW) | Typical Application |
|---|---|---|---|---|---|
| DN 15 | 1/2" | 16.1 | 1.6 Nm³/h | 15 kW | Cooker / Stove Branch |
| DN 20 | 3/4" | 21.7 | 3.2 Nm³/h | 30 kW | 24–28 kW Combi Boiler Branch |
| DN 25 | 1" | 27.3 | 6.0 Nm³/h | 57 kW | Apartment Main Line (Boiler + Stove) |
| DN 32 | 1 1/4" | 36.0 | 12.5 Nm³/h | 119 kW | Small Riser / Cascade Boiler Line |
| DN 40 | 1 1/2" | 41.9 | 19.0 Nm³/h | 181 kW | Multi-Apartment Building Riser |
| DN 50 | 2" | 53.1 | 36.0 Nm³/h | 344 kW | Central Boiler Room Header |
According to standards, natural gas velocity in low-pressure indoor installations is restricted to a maximum of 6 m/s to prevent whistling and regulator wear.