Boiler Flue & Chimney Sizing Guide (EN 13384-1 Standard)

How to calculate boiler chimney inner diameter, cross-sectional area, natural draft pressure, and flue gas velocity under EN 13384-1.

✍️ Emre Cevahir Korkmaz (Mechanical Engineer) 📅 2026-10-02 ⏱️ 4 min read

Proper sizing of boiler chimneys and exhaust flues under EN 13384-1 ensures stable burner operation, adequate natural draft, and safe evacuation of combustion products.

1. Chimney Cross-Sectional Area & Effective Height

Required chimney area (A) is directly proportional to boiler thermal output (Q) and inversely proportional to the square root of effective stack height (√H):

A = (k × Q) / √H

2. Flue Gas Velocity & Material Selection

Natural draft chimneys typically operate at flue gas velocities between 2 and 6 m/s. For high-efficiency condensing boilers with low stack temperatures (45–65 °C), AISI 316L acid-resistant stainless steel flues with condensate drainage are mandatory.

Size your circular or rectangular flue instantly with our Chimney Draft & Size Calculator.