Boiler Flue & Chimney Sizing Guide (EN 13384-1 Standard)
How to calculate boiler chimney inner diameter, cross-sectional area, natural draft pressure, and flue gas velocity under EN 13384-1.
Proper sizing of boiler chimneys and exhaust flues under EN 13384-1 ensures stable burner operation, adequate natural draft, and safe evacuation of combustion products.
1. Chimney Cross-Sectional Area & Effective Height
Required chimney area (A) is directly proportional to boiler thermal output (Q) and inversely proportional to the square root of effective stack height (√H):
A = (k × Q) / √H
2. Flue Gas Velocity & Material Selection
Natural draft chimneys typically operate at flue gas velocities between 2 and 6 m/s. For high-efficiency condensing boilers with low stack temperatures (45–65 °C), AISI 316L acid-resistant stainless steel flues with condensate drainage are mandatory.
Size your circular or rectangular flue instantly with our Chimney Draft & Size Calculator.