Chimney Flue Sizing & Draft Calculator | Muhendis Portal

Calculate boiler chimney diameter, natural thermal draft (Pa) and flue gas flow velocity according to EN 13384-1 standard.

Verified Engineering Calculation Engine

Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.

EN 13384-1 Boiler Flue Chimney Diameter Sizing Chart by Capacity & Height

Recommended circular insulated stainless steel flue inner diameters for natural gas boilers at H=10 m and H=20 m height.

Boiler Capacity (kW)Boiler Capacity (kcal/h)Flue Gas Mass Flow (~kg/h)Dia for H = 10 m (mm)Dia for H = 20 m (mm)
60 kW51,60095 kg/hØ 150 mmØ 130 mm
116 kW100,000185 kg/hØ 180 mmØ 160 mm
233 kW200,000370 kg/hØ 250 mmØ 220 mm
349 kW300,000550 kg/hØ 300 mmØ 250 mm
581 kW500,000920 kg/hØ 350 mmØ 300 mm
1163 kW1,000,0001,840 kg/hØ 500 mmØ 450 mm

Frequently Asked Questions (FAQ)

What creates natural chimney draft?

Natural draft is generated by the difference in density between the hot flue gas inside the chimney and the colder ambient air outside, proportional to chimney effective height.

Related Technical Guides