What creates natural chimney draft?
Natural draft is generated by the difference in density between the hot flue gas inside the chimney and the colder ambient air outside, proportional to chimney effective height.
Calculate boiler chimney diameter, natural thermal draft (Pa) and flue gas flow velocity according to EN 13384-1 standard.
Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.
Recommended circular insulated stainless steel flue inner diameters for natural gas boilers at H=10 m and H=20 m height.
| Boiler Capacity (kW) | Boiler Capacity (kcal/h) | Flue Gas Mass Flow (~kg/h) | Dia for H = 10 m (mm) | Dia for H = 20 m (mm) |
|---|---|---|---|---|
| 60 kW | 51,600 | 95 kg/h | Ø 150 mm | Ø 130 mm |
| 116 kW | 100,000 | 185 kg/h | Ø 180 mm | Ø 160 mm |
| 233 kW | 200,000 | 370 kg/h | Ø 250 mm | Ø 220 mm |
| 349 kW | 300,000 | 550 kg/h | Ø 300 mm | Ø 250 mm |
| 581 kW | 500,000 | 920 kg/h | Ø 350 mm | Ø 300 mm |
| 1163 kW | 1,000,000 | 1,840 kg/h | Ø 500 mm | Ø 450 mm |
Natural draft is generated by the difference in density between the hot flue gas inside the chimney and the colder ambient air outside, proportional to chimney effective height.