Cable Sizing & Voltage Drop Calculation Guide (IEC 60364)
How to calculate copper cable cross-section (mm²) for single-phase (230V) and 3-phase (400V) loads based on current ampacity and voltage drop limits.
✍️ Emre Cevahir Korkmaz (Mechanical Engineer)
📅 2026-09-05
⏱️ 5 min read
When sizing power cables for electric motors, HVAC chillers, pumps, and distribution panels, engineers must verify both current-carrying capacity (ampacity) and percentage voltage drop (%e).
1. Single-Phase and 3-Phase Voltage Drop Formulas
Using copper conductivity κ = 56 m/(Ω·mm²):
- Single-Phase (230V): %e = (200 × L × P) / (κ × S × U²)
- Three-Phase (400V): %e = (100 × L × P) / (κ × S × U²)
Where L is cable length (m), P is active power (W), S is conductor cross-section (mm²), and U is line voltage (V).
2. Permissible Voltage Drop Limits (IEC 60364)
- Lighting Circuits: Max 3%
- Power & Motor Circuits: Max 5%
Verify conductor cross-section and voltage drop instantly with our Cable Size & Voltage Drop Calculator and 3-Phase Motor Power Calculator.