Cable Sizing & Ampacity Calc (IEC 60364) | Muhendis Portal

Select copper electrical cable cross-section (mm²) based on design current, cable installation method, grouping factors and statutory 3% voltage drop.

Verified Engineering Calculation Engine

Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.

IEC 60364 Copper Cable Cross-Section Ampacity & Breaker Sizing Chart

Current-carrying capacity (Ampacity) in conduit and on cable tray, recommended circuit breaker, and max 3-phase power.

Cable Size (mm²)Ampacity in Conduit (A)Ampacity in Air/Tray (A)Recommended Breaker (A)Max 3-Phase Load @ 400V (kW)
1.5 mm²15.5 A19.5 A10 A – 16 A7.5 kW
2.5 mm²21.0 A27.0 A16 A – 20 A11.0 kW
4.0 mm²28.0 A36.0 A25 A15.0 kW
6.0 mm²36.0 A46.0 A32 A18.5 kW
10.0 mm²50.0 A63.0 A40 A – 50 A26.0 kW
16.0 mm²68.0 A85.0 A63 A37.0 kW
25.0 mm²89.0 A112.0 A80 A – 100 A49.0 kW
35.0 mm²110.0 A138.0 A100 A – 125 A60.0 kW

Frequently Asked Questions (FAQ)

What is the maximum allowed voltage drop for motor circuits?

Under standard electrical building regulations (IEC 60364), maximum permitted voltage drop from the main distribution board to final power circuits is typically 3% to 5%.