3-Phase Electric Motor Power Calculator | Muhendis Portal

Calculate active electrical power (kW), current (Amps), power factor (cos φ) and apparent power for three-phase AC electric motors.

Verified Engineering Calculation Engine

Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.

IEC 60034 3-Phase 400V Induction Motor Full-Load Current & Torque Chart

Nominal current (In), IE3 efficiency (η), power factor (cos φ), and rated shaft torque (Mn) for 4-pole (1500 RPM) motors.

Motor Power (kW)Horsepower (HP)Rated Current In @ 400V (A)Efficiency η (%)Power Factor (cos φ)Rated Torque Mn (Nm)
0.75 kW1.0 HP1.75 A82.5%0.785.0 Nm
1.50 kW2.0 HP3.30 A85.3%0.809.9 Nm
2.20 kW3.0 HP4.70 A86.7%0.8114.5 Nm
4.00 kW5.5 HP8.10 A88.6%0.8326.2 Nm
7.50 kW10.0 HP14.70 A90.4%0.8549.0 Nm
11.00 kW15.0 HP21.20 A91.4%0.8671.6 Nm
15.00 kW20.0 HP28.50 A92.1%0.8697.5 Nm
22.00 kW30.0 HP41.00 A93.0%0.87142.5 Nm
37.00 kW50.0 HP68.00 A93.9%0.87239.0 Nm

Frequently Asked Questions (FAQ)

How is 3-phase electric motor current calculated?

Current is calculated via I = P / (√3 × V × cos φ × η), where V is line voltage, cos φ is power factor, and η is electrical motor efficiency.