What is the equal friction method in duct sizing?
It sizes all duct branches maintaining a constant pressure loss per unit length (typically 0.8 to 1.0 Pa/m in comfort systems), simplifying hydraulic balance.
Calculate circular and rectangular air duct dimensions, airflow velocity (m/s) and pressure drop (Pa/m) using the equal friction method.
Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.
Recommended air changes per hour (ACH), main duct velocity, branch duct velocity, and diffuser neck velocity.
| Space / Application Type | Air Changes (ACH - 1/h) | Main Duct Velocity (m/s) | Branch Velocity (m/s) | Diffuser Velocity (m/s) |
|---|---|---|---|---|
| Residential / Hotel Room | 4 – 6 | 5.0 – 6.5 | 3.5 – 4.5 | 1.5 – 2.2 |
| Office / Conference Room | 6 – 10 | 6.0 – 8.0 | 4.0 – 5.5 | 2.0 – 2.8 |
| Restaurant / Cafeteria | 10 – 15 | 7.0 – 9.0 | 5.0 – 6.0 | 2.5 – 3.5 |
| Commercial Kitchen Exhaust | 20 – 35 | 9.0 – 12.0 | 7.0 – 9.0 | 3.5 – 5.0 |
| Underground Parking Garage | 6 – 10 | 8.0 – 11.0 | 6.0 – 8.0 | 4.0 – 5.0 |
| Industrial Workshop / Plant | 8 – 15 | 9.0 – 13.0 | 6.0 – 9.0 | 3.5 – 5.0 |
It sizes all duct branches maintaining a constant pressure loss per unit length (typically 0.8 to 1.0 Pa/m in comfort systems), simplifying hydraulic balance.