HVAC Duct Sizing Guide: Equal Friction Method & Velocity Limits
Learn how to size rectangular and circular HVAC air ducts using air changes per hour (ACH), acoustic velocity limits, and the equal friction method.
✍️ Emre Cevahir Korkmaz (Mechanical Engineer)
📅 2026-08-14
⏱️ 6 min read
Properly sized ventilation ductwork delivers conditioned air quietly while minimizing fan static pressure and electrical power consumption.
Determining Airflow Rate (Q) and Cross-Sectional Area (A)
Airflow demand is determined from occupancy fresh-air rates or room Air Changes per Hour (ACH):
Q (m³/h) = Room Volume (m³) × ACH (1/h)
Duct Area A (m²) = Q (m³/s) / V (m/s)
Recommended Air Velocity Limits & Equal Friction Design
- Main Supply/Return Trunks: 6 – 8 m/s (commercial), 8 – 11 m/s (industrial)
- Branch Ducts: 4 – 6 m/s
- Diffuser Connections: 2 – 3 m/s
In the Equal Friction Method, ducts are sized for a constant linear pressure drop (typically 0.8 to 1.0 Pa/m), using the Huebscher equivalent diameter formula to convert between circular and rectangular sections. Size your ductwork instantly with our HVAC Duct Sizing Calculator.