HVAC Room Cooling Load Calculator | Muhendis Portal

Determine sensible and latent heat gains from building envelope, solar radiation, lighting, machines, and occupants for HVAC system design.

Verified Engineering Calculation Engine

Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.

ASHRAE Occupant Sensible & Latent Heat Gain & Cooling Load Reference Chart

Standard sensible and latent heat gains per person (W) and typical specific cooling load density (W/m²).

Activity / Space TypeSensible Heat / Person (W)Latent Heat / Person (W)Total Heat / Person (W)Specific Cooling Load (W/m²)
Seated Office Work70 W45 W115 W110 – 140 W/m²
Restaurant / Dining75 W85 W160 W180 – 250 W/m²
Retail Store / Standing75 W70 W145 W140 – 190 W/m²
Light Bench / Assembly Work80 W140 W220 W160 – 220 W/m²
Gymnasium / Heavy Exercise150 W275 W425 W220 – 320 W/m²

Frequently Asked Questions (FAQ)

What is the difference between sensible and latent cooling load?

Sensible heat increases dry-bulb temperature (from walls, windows, lights), while latent heat represents moisture added by human respiration and infiltration.