What temperature should domestic hot water be stored at?
DHW is typically stored at 60°C to prevent Legionella pneumophila bacterial proliferation while being blended to 45°C - 50°C at points of use.
Determine DHW storage cylinder capacity (liters) and heat exchanger coil rating (kW) for residential buildings, hotels and hospitals.
Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.
Standard calorifier tank volume, hourly recovery rate (10°C to 60°C), heating coil power (kW), and coil surface area (m²).
| Building Type / Size | Calorifier Volume (L) | Recovery Rate (L/h) | Heating Coil Power (kW) | Coil Surface Area (m²) |
|---|---|---|---|---|
| Large Villa (2–3 Bathrooms) | 200 – 300 L | 450 L/h | 26 kW | 1.4 m² |
| 10 – 16 Apartments | 500 L | 850 L/h | 50 kW | 2.2 m² |
| 20 – 30 Apartments | 1,000 L | 1,500 L/h | 87 kW | 3.8 m² |
| 40 – 60 Room Hotel | 2,000 L | 2,800 L/h | 163 kW | 6.5 m² |
| 80 – 120 Room Hotel / Hospital | 3,000 L | 4,200 L/h | 244 kW | 9.5 m² |
DHW is typically stored at 60°C to prevent Legionella pneumophila bacterial proliferation while being blended to 45°C - 50°C at points of use.