DHW Calorifier & Storage Tank Sizing | Muhendis Portal

Determine DHW storage cylinder capacity (liters) and heat exchanger coil rating (kW) for residential buildings, hotels and hospitals.

Verified Engineering Calculation Engine

Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.

Domestic Hot Water Calorifier (Storage Tank) Volume & Coil Power Chart

Standard calorifier tank volume, hourly recovery rate (10°C to 60°C), heating coil power (kW), and coil surface area (m²).

Building Type / SizeCalorifier Volume (L)Recovery Rate (L/h)Heating Coil Power (kW)Coil Surface Area (m²)
Large Villa (2–3 Bathrooms)200 – 300 L450 L/h26 kW1.4 m²
10 – 16 Apartments500 L850 L/h50 kW2.2 m²
20 – 30 Apartments1,000 L1,500 L/h87 kW3.8 m²
40 – 60 Room Hotel2,000 L2,800 L/h163 kW6.5 m²
80 – 120 Room Hotel / Hospital3,000 L4,200 L/h244 kW9.5 m²

Frequently Asked Questions (FAQ)

What temperature should domestic hot water be stored at?

DHW is typically stored at 60°C to prevent Legionella pneumophila bacterial proliferation while being blended to 45°C - 50°C at points of use.