Why is a membrane pressure tank necessary for booster pumps?
The pressure vessel cushions water hammer, maintains system pressure during minor withdrawals, and prevents frequent on/off cycling that burns pump motors.
Calculate residential and commercial water booster pump flow rate (m³/h), delivery pressure head (bar) and pressure membrane vessel volume.
Engineered for mechanical, HVAC, piping, and design engineers in compliance with international standards (ISO, DIN, EN, ASME, ASHRAE). Load the interactive tool for real-time calculations and automated reports.
Recommended booster pump flow rate (m³/h), operating pressure (bar), and domestic water storage volume.
| Number of Apartments | Floors | Simultaneity Factor | Pump Flow Q (m³/h) | Total Head Hm (m / bar) | Water Tank Volume (m³) |
|---|---|---|---|---|---|
| 8 Apartments | 4 Floors | 0.42 | 3.5 m³/h | 45 m (4.5 bar) | 5 m³ |
| 12 Apartments | 5 Floors | 0.36 | 4.5 m³/h | 50 m (5.0 bar) | 8 m³ |
| 20 Apartments | 6 Floors | 0.30 | 6.5 m³/h | 55 m (5.5 bar) | 12 m³ |
| 32 Apartments | 8 Floors | 0.25 | 9.0 m³/h | 65 m (6.5 bar) | 20 m³ |
| 48 Apartments | 10 Floors | 0.22 | 12.5 m³/h | 75 m (7.5 bar) | 30 m³ |
| 80 Apartments | 14 Floors | 0.18 | 18.0 m³/h | 90 m (9.0 bar) | 50 m³ |
The pressure vessel cushions water hammer, maintains system pressure during minor withdrawals, and prevents frequent on/off cycling that burns pump motors.