Closed Expansion Tank Sizing Formula & Pre-Charge Pressure Guide

How to calculate expansion vessel volume (Vn), water expansion volume (Ve), and nitrogen pre-charge pressure (P0) for closed-loop hydronic systems.

✍️ Emre Cevahir Korkmaz (Mechanical Engineer) 📅 2026-08-11 ⏱️ 4 min read

Water expands when heated inside a closed hydronic loop. Without a properly sized diaphragm expansion tank, system pressure will rapidly exceed the safety relief valve limit.

Water Expansion Volume (Ve) and Nominal Tank Volume (Vn)

First, determine the total system water volume (Vs, Liters) and multiply by the expansion factor (n ≈ 0.0355 for 10 °C to 90 °C):

Ve = Vs × n

Then calculate the nominal expansion vessel volume (Vn) from the pre-charge pressure (P0) and maximum operating pressure (Pmax):

Vn = Ve × [ (Pmax + 1) / (Pmax - P0) ]

Setting Pre-Charge Pressure (P0)

Pre-charge pressure P0 (bar) must equal the static building height (Hst / 10) plus 0.2 to 0.3 bar positive head margin at the highest radiator. Compute your exact vessel size with our Expansion Tank Sizing Calculator.